600 Larkin Street
Industrial building
-
1962
Built as the Pacific Gas and Electric Company building, electrical substation. One storey.
-
Jul 2002
Street space and sidewalk.
-
Oct 2005
Reroofing.
-
Mar 2007
Performing a voluntary seismic strengthening of the electric substation including strengthening exterior connections, shear connection, constructing new shearwall & horizontal bracing & strengthening low roof diaphragm. see attached project description.
-
Jul 2007
Reroofing.
-
Nov 2007
A new nfs2-3030 panel with 1 remote graphic annunicator. the system will include 40 smokes, 6 beam detectors, 1 pull station, 6 dual monitor modules, 6 monitor modules, 6 pull station for existing deluxe system & 1 weatherproof hornstrobe.
-
Nov 2007
Add new wet sprinkler system 15 heads in oil holding/over flow room & add new 39 nozzle water spram/deluge system on first floor transformer.
-
Jun 2008
Reinstall heat detectors in transformer bank #5 for activation of the deluge sprinkler system. the system shall include 6 heat detectors around transformer bank #5.
-
Dec 2008
Replace existing water spray system at transformer bank 4 with new water spray system (deluge).
-
Dec 2008
Replace nozzles on existing water spray system protecting transformer bank 5, reference permit application 2007-1119-8527.
-
Dec 2008
Reinstall 6 heat detectors in transformer bay #4 for activation of the deluge sprinkler system on ground floor.
-
Mar 2010
Replace existing water spray system at transformer bank #1 with new water spray system for the new transformer, existing deluge system.
-
Mar 2010
Pg&e sub-station. to supply and install 6 heat detectors in transformer bank # 1 for activation of the existing deluge sprinkler system.
-
Jul 2013
Fire alarm system expansion and replace the graphic annunciator. remove and replace the sprinkler manifold down the basement. also install deluge system in bank 2 area to protect the new transformer.
-
Jul 2014
Construct partition walls between transformers 3 and 4 on 1st floor - 24 ft and 16.5 ft high of pre-concrete. maher n/a. must maintain existing fire suppression coverage.
-
Sep 2014
Replace existing deluge & heat detection system to accommodate new transformer. ** maher: compliance with ordinance no# 155-13 not required **.
-
Jan 2016
Construct partition wall between transformers 5 & 6 which will be 16 ft in height and 56 feet in length. maher na.
-
Feb 2016
1st floor: install replacement deluge system at transformer 6. install new pilot sprinkler - release for tb 5 and 6. relocate pipe stand for blast wall at tb 5 and 6, install pipe stands & nozzles per floor by tb - 5. maher na.
-
Feb 2017
Design and expand existing fire alarm system to cover the new building addition, ref permit application 201511233360, add 1 power supply, 9 notification, 19 initiating. note: lots have been merged, to block 0335 lot 037. n/a ordinance #155-13.
-
Dec 2017
Remove existing 4"x3"(2-way)fire depart connection and relocate on same side of building 30' to west. ref app#201601086709. n/a for maher.
-
Jun 2018
Fire alarm as builts ref 201702068696.
-
Sep 2022
To obtain final inspection for work approved under permit application # 2018-0620-2489. all work is complete.
-
Jul 2025
Replace existing fence with 10" high fence as mandated by cpuc.
-
Apr 2026
Reroofing no hot works carlisle syntec systems/fleeceback tpo; solar reflectance 0.70, thermal emittance 0.90, solar reflectance index 99.
DBI holds 39 permits for this parcel, most of them tenant improvements on individual floors. The timeline shows the 24 largest by stated cost, plus the earliest on file; the DBI query in the sources below returns all 39. 11 of them are nominal $1 street-space or sidewalk permits. 1 expired permit is not shown.