401–405 Folsom Street
East Cut · San Francisco, CA 94105
Permit history
-
Oct 2000
Alter existing wet fire sprinkler system at (basement) new ventilation rms (2ea), install n/direct i.
-
Oct 2005
Reroofing.
-
Nov 2007
An intelligent nfs 640-2 control apnel with (1) graphic annunciator panel. the system will include (31) smokes, (9) beam detectors, (2) pull stations, (18) dual monitor modules, (6) control modules, (1) monitor module for existing deluge & wet sprinkler systems, (2) weatherproof horn/strobes.
-
May 2011
Pg&e is installing two fire resistant partition walls between the existing transformers on the 1st floor.
-
Apr 2012
Demolition existing deluge system in bank 3 to re-install to accommodate new transformer on the 1st floor. modify bank 13 and replace after blast wall has been installed. (total 36 spray nozzles) install detection system for bank 3.
-
Feb 2014
Demolition existing tb2 & tb12 deluge system & existing valve, demolition existing backflow prev & strainer. install new main shutoff valve in stairwell by entry. install new piping in bank tb2 & tb12 with wet pilot system, install new backflow & striners, install new tb2 & 12 deluge valve. install 4 new duct detectors, 5 new.
-
Feb 2014
Construction partition wall between transformer 2 & 12 to protect them, the wall will be 20' height, 17 long & 1' wide - pre cast refinforced refactory concrete panels & columns wiht the top being supported to the wall with steel bracings.
-
Aug 2014
Cosco to design & expand fire alarm system to cover the scope work. remove existing fan control, install new fan control in lobby. interface fan control with fire alarm system. remove existing graphic annuciator & install new touch graphic annunciator in lobby. upgrade elevator recall system.
-
Jul 2015
Relocate e valves in basement. install f500 system consisting of 900 gal bladder tank, concentrate line, modify piping at sw corner of building for new oil containment area.
-
Sep 2015
Expand fire alarm system to monitor the new sprinkler deluge system.
-
Feb 2017
Temporarily remove existing deluge piping at tb2 & 12 for transformer maintenance. restore system after maintenance is complete. remove the existing fire supression system piping in ocb 202.
-
Feb 2017
Demolition of existing deluge detecting system protecting cb202.
-
Feb 2017
Demolition of the existing deluge detection system protecting hz2.
-
Feb 2017
Remove the existing fire supression system piping in hz-2.
-
May 2017
1/f #tb1 & 11- remove existing deluge system piping for transformer maintenance, restore system after maintenance is complete, replace existing heat detections system with pneumatic detection (pilot line).
-
May 2017
1/f #tb1 & 11- demolition of existing deluge detection system protecting tb1 & 11.
-
May 2018
Replace existing transformer deluge system piping and install new piping to match new transformer.
-
Apr 2019
Demolish existing deluge protection for system protecting tb 5 & 15. design & install new deluge system protecting tb 5 & 15 from existing single feed supplied with f-500 encapsulating agent. system designed at 0.30 gpm/sq ft over transformer surface & 0.15 gpm/sq ft over floor area.
-
Jun 2019
Install new conduit & 4 new h/d (replacing exist) h/d to exist building.
-
Sep 2019
Provide design, permit, parts, labor associated to 4 new vfd fan units to interface with existing fa system & shut down upon alarm activation.
-
Jun 2021
Demolition existing fire alarm devices within bank 1-11 space and re-install full heat detector add hvac duct smoke detection monitoring & hvac shutdown and audio/visual coverage once transformer is installed.
-
Jul 2021
Adding f500 tank and tamper switch monitoring point into the existing fire alarm system.
-
Sep 2021
Demolition existing deluge systems protecting t8 1/11 design and install new system protecting new transfomer 1 and existing transformer 11.
-
Apr 2026
Reroofing no hot work. crrc #0628-0028.
DBI holds 41 permits for this parcel, most of them tenant improvements on individual floors. The timeline shows the 24 largest by stated cost, plus the earliest on file; the DBI query in the sources below returns all 41. 14 of them are nominal $1 street-space or sidewalk permits.
Not yet documented: the developer, the early tenants and the date of the last recorded sale. The assessor dates the building to 1900; Planning's historic resource survey records 1973. Submit an update